![]()
SECTION 5-8 ILLUMINATION OF MEANS OF EGRESS
5-8.1 General.
5-8.1.1 Illumination of means of egress shall be provided in accordance
with section 7.8 for every building and structure where required in Chapters 11
through 42. For the purposes of this requirement, exit access shall include
only designated stairs, aisles, corridors, ramps, escalators, and passageways
leading to an exit.
5-8.1.2 Illumination of means of egress shall be continuous during the
time that the conditions of occupancy require that the means of egress be
available for use. Artificial lighting shall be employed at such places and for
such periods of time as required to maintain the illumination to the minimum footcandle {Lux(lx)} values herein specified.
5-8.1.3* The floors of means of egress shall be illuminated at all
points including angles and intersections of corridors and passageways,
stairways, landings of stairs, and exit doors to values of not less than 1 footcandle (10 lx) measured at the floor. Exception: In
assembly occupancies, the illumination of the floors of exit access shall be
not less than 1/5 footcandle (2 lx) during periods of
performances or projections involving directed light.
5-8.1.4 Any required illumination shall be so arranged that the failure
of any single lighting unit, such as the burning out of an electric bulb, will
not leave any area in darkness.
5-8.1.5 The equipment or units installed to meet the requirements of
Section 5-10 shall be permitted also to serve the function of illumination of
means of egress, provided that all applicable requirements of this section for
such illumination are also met.
5-8.2 Sources of Illumination.
5-8.2.1 Illumination of means of egress shall be from a source of
reasonably assured reliability, such as public utility electric service.
5-8.2.2 No battery-operated electric light nor
any type of portable lamp or lantern shall be used for primary illumination of
means of egress. Battery-operated electric lights shall be permitted to be used
as an emergency source to the extent permitted under Section 5-9, “Emergency
Lighting.”
SECTION 5-9 EMERGENCY LIGHTING
5-9.1 General.
5-9.1.1 Emergency lighting facilities for means of egress shall be
provided in accordance with this section for every building or structure where
required in Chapters 8 through 30. For the purposes of this requirement, exit
access shall include only designated stairs, aisles, corridors, ramps,
escalators, and passageways leading to an exit.
5-9.1.2 Where maintenance of illumination depends upon changing from one
energy source to another, there shall be no appreciable interruption of
illumination during the changeover. Where emergency lighting is provided by a
prime mover-operated electric generator, a delay of not more than 10 seconds
shall be permitted.
5-9.2 Performance of System.
5-9.2.1* Emergency illumination shall be provided for a period of 1 1/2
hours in the event of failure of normal lighting. Emergency lighting facilities
shall be arranged to provide initial illumination that is no less than an
average of 1 footcandle (10 lx) and a minimum at any
point of .1 footcandle (1 lx) measured along the path
of egress at floor level. Illumination levels may decline to .6 footcandle (6 lx) average and a minimum at any point of .06
footcandle (.6 lx) at the end of the emergency
lighting time duration. A maximum to minimum illumination uniformity ratio of
40 to 1 shall not be exceeded.
5-9.2.2* The emergency lighting system shall be so arranged as to
provide the required illumination automatically in the event of any
interruption of normal lighting, such as any failure of public utility or other
outside electrical power supply, opening of a circuit breaker or fuse, or any
manual act(s), including accidental opening of a switch controlling normal
lighting facilities.
5-9.2.3 Emergency generators used to provide power to emergency lighting
systems shall be installed, tested, and maintained in accordance with NFPA 110,
Emergency and Standby Power Systems.
5-9.2.4* Battery-operated emergency lights shall use only reliable types
of rechargeable batteries provided with suitable facilities for maintaining
them in properly charged condition. Batteries used in such lights or units
shall be approved for their intended use and shall comply with NFPA 70,
National Electrical Code.®
5-9.2.5 The emergency lighting system shall be either
continuously in operation or capable of repeated automatic
operation without manual intervention.
5-9.3 Testing and Maintenance. (See Section 31-1.)
SECTION 5-10 MARKING OF MEANS OF EGRESS
5-10.1 General.
5-10.1.1 Means of egress shall be marked in accordance with this section
where required in Chapters 8 through 30.
5-10.1.2* Exits shall be marked by an approved sign readily visible from
any direction of exit access.
Exception: Main exterior exit doors that obviously and clearly are identifiable
as exits.
5-10.1.3 Access to exits shall be marked by approved readily visible
signs in all cases where the exit or way to reach it is not readily apparent to
the occupants. Sign placement shall be such that no point in the exit access is
more than 100 ft (30 m) from the nearest visible sign.
Exception: Signs in existing buildings need not meet the 100-ft (30 m) distance
requirement.
5-10.1.4* Where floor proximity exit signs are specifically required by
Chapters 8 through 30, exit signs shall be placed near the floor level in
addition to those signs required for doors or corridors by 5-10.1.2 and 5-10.1.3.
These signs shall be sized and illuminated in accordance with the requirements
of 5-10.2 and 5-10.3. The bottom of the sign shall be not less than 6 in. (15.2
cm) nor more than 8 in. (20.3 cm) above the floor. For
exit doors, the sign shall be mounted on the door or adjacent to the door with
the closest edge of the sign within 4 in.(10.2cm) of
the door frame.
5-10.1.5* Every sign required by Section 5-10
shall be so
located and of such size, distinctive color, and design as to be readily
visible and shall provide contrast with decorations, interior finish, or other
signs. No decorations, furnishings, or equipment that impair visibility of an
exit sign shall be permitted, nor shall there be any brightly illuminated sign
(for other than exit purposes), display, or object in or near the line of
vision of the required exit sign of such a character as to so detract attention
from the exit sign.
5-10.1.6 Where floor proximity egress path marking is specifically
required by Chapters 8 through 30, a listed and approved floor proximity egress
path marking system that is internally illuminated shall be installed within 8
in. (20.3 cm) of the floor. The system shall provide a visible delineation of
the path of travel along the designated exit access and shall be essentially
continuous, except as interrupted by doorways, hallways, corridors, or other
such architectural features. The system shall operate continuously or at any
time the building fire alarm system is activated. The activation, duration, and
continuity of operation of the system shall be in accordance with 5-9.2.
5-10.2* Size of Signs.
5-10.2.1 Externally illuminated signs required by 5-10.1 and 5-10.4.11
shall have the word “EXIT” or other appropriate wording in plainly legible
letters not less than 6 in. (15.2 cm) high with the principal strokes of
letters not less than 3/4 in. (1.9 cm) wide. The word “EXIT” shall have letters
of a width not less than 2 in. (5 cm) except the
letter “I,” and the minimum spacing between letters shall be not less than 3/8 in.
(1 cm). Signs larger than the minimum established in this paragraph shall have
letter widths, strokes, and spacing in proportion to their height.
Exception No. 1: Existing approved signs.
Exception No. 2: Existing signs having the required
wording in plainly legible letters not less than 4 in. (10.2 cm) high.
Exception No. 3: Marking required by 5-10.1.3 and 5-10.1.7
5-10.2.2 Internally illuminated signs required by 5-10.1 and 5-10.4.1.1
shall have the word “EXIT” or other appropriate wording in letters legible from
a distance of at least 100 ft (30 m) under all normal and emergency lighting
conditions (30 fc and 1 fc,
respectively). Internally illuminated signs shall be listed in accordance with
UL 924.
Exception No. 1: Approved exit signs.
Exception No. 2: Existing signs having the required wording in legible letters
not less than 4 in. (10.2 cm).
Exception No. 3: Marking required by 5-10.1.3 and 5-10.1.7.
5-10.3 Illumination of Signs.
5-10.3.1* Every sign required by 5-10.1.2 or
5-10.1.3 shall be suitably illuminated by a reliable light source. Externally
and internally illuminated signs shall be visible in both the normal and
emergency lighting mode.
5-10.3.2* Externally illuminated signs shall be
illuminated by not less than 5 footcandles (54 lx) and
shall employ a contrast ratio of not less than 0.5.
5-10.3.3* The visibility of an internally
illuminated sign shall be the equivalent of an externally illuminated sign that
complies with 5-10.3.2.
Exception No. 1: Approved existing signs.
Exception No. 2*: Listed self-luminous or electroluminescent signs that provide
evenly illuminated letters shall have a minimum luminance of 0.06 footlamberts (0.21 cd/sq m) as
measured by a color-corrected photometer. New signs shall be located such that
viewing distance along the path of egress is not more than their marked rating.
5-10.3.4 Every sign required by 5-10.1.4 shall provide evenly
illuminated letters having a minimum luminance of 0.06 footlamberts
(0.21 cd/sq m).
Exception: Signs complying with the requirements of 5-10.3.3 are acceptable.
5-10.3.5 Every sign required to be illuminated by 5-10.3 shall be
continuously illuminated as required under the provisions of Section 5-8.
Exception*: Illumination for signs shall be permitted to flash
on and off upon activation of the fire alarm system.
5-10.3.6 Where emergency lighting facilities are required by the
applicable provisions of Chapters 8 through 30 for individual occupancies, the
exit signs, except approved self-luminous signs, shall be illuminated by the
emergency lighting facilities. The level of illumination of the exit sign shall
be at the levels provided in accordance with 5-10.3.2 or 5-10.3.3 for the
required emergency lighting time duration as specified in 5-9.2.1 but shall be
permitted to decline to 60 percent of the illumination level at the end of the
emergency lighting time duration.
5-10.4 Specific Requirements.
5-10.4.1 Directional Signs.
5-10.4.1.1* A sign complying with 5-10.2 reading “EXIT” or a similar
designation with a directional indicator showing the direction of travel shall
be placed in every location where the direction of travel to reach the nearest
exit is not apparent. Directional signs shall be listed.
NOTICE: Following the issuance of this edition, an appeal was filed requesting
that 5-10.4.1.2 revert to the wording in the 1988 edition of the Code. Refer to
page 101-11.
5-10.4.1.2* Directional Indicator. The
directional indicator shall be located outside of the EXIT legend, not less
than 3/8 in. (1 cm) from any letter, and may be integral to or separate from
the sign body. The directional indicator shall be of a chevron type as shown in
Figure 5-10.4.1.2 and shall be identifiable as a directional indicator at a
minimum distance of 40 ft (12 m) under all space illumination conditions. The
directional indicators shall not be located at the end of the sign opposite the
direction indicated.
Exception: Existing approved signs.
Figure 5-10.4.1.2
5-10.4.2* Special Signs. Any door, passage, or stairway that is
neither an exit nor a way of exit access and that is so located or arranged
that it is likely to be mistaken for an exit shall be identified by a sign
reading “NO EXIT.” Such sign shall have the word “NO” in letters 2 in. (5 cm)
high with stroke width of 3/8 in. (1 cm) and the word EXIT in letters 1 in.
(2.5 cm) high, with the word EXIT below the word NO.
Exception: Approved existing signs.
Figure 5-10.4.1.2
SECTION 31-1 OPERATING FEATURES, GEN. REQUIREMENTS
31-1.3.7 Periodic Testing of Emergency Lighting Equipment. A functional
test shall be conducted on every required emergency lighting system at 30-day
intervals for a minimum of 30 seconds. An annual test shall be conducted for
the 1 1/2 hour duration of the test. Written records of visual inspections and
tests shall be kept by the owner for inspection by the authority having
jurisdiction.
Exception: Self-testing/self-diagnostic, battery-operated emergency lighting
equipment that automatically performs a minimum 30-second test and diagnostic
routine at least once every 30 days and indicates failures by a status
indicator shall be exempt from the 30-day functional test, provided a visual
inspection is performed at 30-day intervals.